SAFECOAT LATEX ®

Test Results
Testing was conducted in accordance with ASTM E84 and CAN4-S102 "Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies" by Underwriters Laboratories of Canada. Following is a summary of the results of those tests

Material 1FSR 2SDC
Douglas Fir Lumber, coated by SAFECOAT LATEX ® with a single coat at a rate of 3. 7 m2 per liter. 5 5
S-P-F Plywood Coated by SAFECOAT LATEX ® with a single coat at a rate of 3.7m2 per liter and a single coat of Safecoat 725 overcoat at 7.4m2 per liter.(3) 5 0
Oriented Strand Board 10 mm nominal thickness, coated by SAFECOAT LATEX ® with a single coat at a rate of 3.7 m2 per liter 10 10-25
High density polyurethane foam coated with SAFECOAT LATEX ® at 80 ft2/USG <25 <150

1 FSR - flame spread rating
2 SDC - smoke developed classification
3 Safecoat 725 is not a fire retardant but is used solely to change gloss and scrubbability of the Safecoat Latex ®

NOTE: The flammability characteristics of different species of lumber vary. However, the practice of using Douglas Fir as a standard test substrate provides a basis for the comparison of various coatings. Oriented Strand Board (OSB) has a very high flame spread rating and as such requires an individual fire test as shown above. Do not extrapolate OSB Flame Spread rating based on Douglas Fir test results.

It is accepted that the above mentioned values for Douglas Fir can be attributed to other species of lumber predicted to have a flame spread of 100 or less providing the lumber is minimum nominal 25 mm thick. These other species include:

Eastern White Pine Western Hemlock
Lodgepole Pine Western Red Cedar
Pacific Coast Yellow Cedar Western White Pine
Select Red Oak Flooring White Spruce


FIRE RESSISTANCE RATING

Testing was conducted in accordance with ASTM E-119 “Floor/Open Ceiling Assembly Fire Test” and NFPA 251 "Small Scale Test” by Guardian Fire Testing Laboratories Inc. of Buffalo, NY. Following is a summary of results:

Assembly Time to Flame-Through
NO GYPSUM - 2” x 10” nominal SPF floor joists, 16” on centre. 3/4” oriented strand board, tongue and groove flooring. Underside assembly coated with SAFECOAT LATEX ® with 2 coats at a rate of 7.4 m2/L (300 ft2/gal) each coat. 46 minutes, 37 seconds
WITH GYPSUM - 2” X 10” nominal SPF floor joists, 1 16” on centre. 3/4” oriented strand 4 5 minutes
board, tongue and groove flooring. Ceiling: 5/8” type X gypsum wallboard. Exposed side of
gypsum coated with 2 coats of SAFECOAT LATEX ® at a rate of 7.4m2/L (300 ft2/gal) each coat.
1 hour, 45 minutes

Identification and Certification
Each container bears a label reading "Underwriters Laboratories of Canada" or
"Warnock Hersey Laboratories of Canada - Listed - Fire Retardant Coating" and
"Class A Thermal Barrier"
.

Guarantee/Warranty:
Recommendations for the use of our products are based on tests carried out at government approved labs. Manufacturer and seller are not responsible for results where the product is used under conditions beyond our control. Under no circumstances will They be liable for consequential damages or damages to anyone in excess of the purchase price of the product or services.